With test leads, power supply, PC software and case.
KE-FLB | |
---|---|
Loop resistance | Measuring range 1 Ω – 10 kΩ Accuracy 100 Ω – 10 kΩ: ± 0.2% MV ± 0,1 Ω ± 1 digit |
Resistance difference (ΔR) | Measuring range of R 1 Ω – 5 kΩ Measuring range of ΔR 1 Ω – 1 kΩ Accuracy ΔR 1 Ω – 10 Ω: ± 1% FV ± 0.1 Ω 10 Ω – 100 Ω: ± 1% – ± 0.2% FV ± 0.1 Ω 100 Ω – 1 kΩ: ± 0,2% FV ± .,05 Ω |
Insulation resistance | Measuring range 10 kΩ – 100 (20.000) MΩ Accuracy 100 kΩ – 10 MΩ: ± 1% MV ± 1 digit 10 MΩ – 100 MΩ: ± 2% MV 100 MΩ – 3 GΩ: ± 10% MV 3 GΩ – 10 GΩ: ± 20% MV 10 GΩ – 20 GΩ: ± 30% MV |
Capacity | Measuring range 1 nF – 10 (25) μF tan δ: 0.0001 – 0.1 Accuracy 1 nF – 10 μF: ± 0.5% MV ± 1 digit Measuring range 11 Hz |
DC fault locations | Measuring methods: Murray Loop, Three Point, Improved Hector (Küpfmüller) Loop resistance range 1 Ω – 10 kΩ AccuracyLx/L (Rs = 2kΩ, Lx/L = 0,1 bis 1) Fault < 1 MΩ ± 0.1% MV ± 1 digit Fault 1 – 5 MΩ ± 0.2% MV ± 1 digit Fault 5 – 25 MΩ ± 1% MV ± 1 digit Fault 25 – 100 MΩ ± 5% MV ± 1 digit Measuring voltage max. 100 V Internaln filter > 70 dB at 50 Hz Measuring current max. 400 μA Stored cable parameters: Standard Cu and Al cables, User defined cables, User defined MultiSection cables, User defined Loaded cables |
AC fault location | Wire break with or without leakage Measuring range depending on cable up to 20 km Accuracy of Lx/L 20 nF– 10 μF: ± 0.2 – 1% MV ± 1 digit Measuring frequency 11 Hz Split location Measuring range depending on cable up to 20 km Accuracy of Lx/L and L2/L 20 nF – 10 μF: ± 0.2 – 1% MV ± 1 digit Measuring frequency 11 HZ |
Voltage measurement | DC voltage 0 – 100 V AC voltage 0 – 100 V(eff= Accuracy (DC u. AC at 50/60 Hz): ± 1% MW ± 0,1 V Frequency range 15 – 300 Hz |
Temperature (with Pt 1000 temperature probe) | Temperature range -20 – +60 °C Resolution 0.1 °C Accuracy ± 0.4 °C |
Storage and print of measurement results | Memory for 128 result displays Print from result display or from memory via RS232CSchnittstelle transferrable to PC |
Connectors | Conn. f. measuring cables: 4 mm safety banana sockets Interface f. RS232C: D Sub9 Charger: 2.1 / 5.5 mm |
Power supply | Internal rechargeable battery pack, operation time approx. 8 hours Ext. charging via charger 230V, 50/60 Hz / via 12 V car charger Charging time (fast charging) < 3 Hours |
Auto power down | After 10 minutes without keystroke |
Display | 192 x 192 pixel graphic LCD with backlight with autom. power down (5 mm) |
Input protection | 100 V(eff.) 50 Hz, 140 V DC, 100 mA(PEAK) , für 30 s |
Dimensions | 200 mm x 100 mm x 40 mm |
Weight | 0.8 kg |
Environmental conditions | Reference range +23 ± 5 °C: RH 30 % – 75 %* Specified operating range 0 – 40 °C: RH 30 % – 75 % (< 25 g/m3)* Operating range limits -10 – 50 °C: RH 30 % – 75 % (< 25 g/m3)* Transport / Storage range limits -20 – 70 °C: RH 30 % – 75 % (< 35 g/m3)* * no condensation |